CLICK HERE FOR ADOBE PDF FILE OF THIS
ARTICLE
How to Avoid
Common Floor
Problems
In any given year our staff will
inspect as many as two hundred industrial floor slabs, all of
which have problems to some degree. While problems vary in
severity from project to project, they are seldom unique. Rather,
they tend to be the result of the same mistakes time and time
again.
The purpose of this technical paper is to share our observations
in the hope that you can avoid these common mistakes on your
current or future projects.
PROBLEMS IN THE
DESIGN PHASE
1. Loosely Drafted
Construction Documents
When contractors review plans and specs they can soon determine
the capabilities of the designer and "the tone" of the
project. A tightly drafted floor spec and complete floor details
will tell the contractor that the floor is of critical
importance. Avoid wide open material and procedural specs that
basically allow the contractor to design the floor. Show the
proposed joint layout, provide complete jointing details, specify
allowable concrete additives, list acceptable products by name,
minimize the use of the broad term "or equal." In
construction, the term "or equal" is often interpreted
as "or cheaper."
By drafting tight construction documents you are not saying that
you won't listen to a concrete contractor's suggestions, many of
which may be excellent. You are simply making it incumbent upon
him to fully justify each recommendation.
2. Specifying or
Allowing Additives
There are numerous concrete additives on the market, all claiming
wonderful benefits. But what is not always apparent are the
possible side effects the additives cause. For example, some
additives delay the appearance of bleed water, thus delaying the
finishing. Others may allow more rapid slab shrinkage, adding to
curl problems.
Concrete additives can be helpful in achieving certain results
(better finishing characteristics, etc.), but they should never
be considered a substitute for a good basic mix design, proper
placement by qualified contractors and adequate curing.
3. Minimize
Shrinkage and Curl
Excessive (or rapid) shrinkage and slab edge curl can affect even
the best designed floor. You can minimize shrinkage and curl by
paying attention to the proper mix design.
a. Use the largest aggregate possible.
Coarse aggregate occupies space with shrinking.
b. Water and cement both add significantly to shrinkage and curl.
Insist upon a low water/cement ratio from the ready mix supplier.
c. Avoid high strength concrete mixes. Concrete strength is
measured by compressive strength, and floors seldom, if ever,
fail in compression. To achieve higher strengths you must use
more cement, which adds to shrinkage and curl.
Many in the industry equate low slump with low shrinkage. This is
true to a degree, but aggregate size and water/cement ratio are
likely of greater importance.
4. Joint Spacing;
Closer, More Square
The trend over the past decade has been to make slab panels
larger, and thus have fewer joints. The reasons most commonly
cited are:
a. It costs money to create and fill more
joints.
b. In theory, it costs the owner more in floor maintenance if he
has more joints.
c. Designers are extending the spacing between columns, which in
turn tends to extend joint spacing.
These reasons are all valid, but we often fail to consider the
effect of normal shrinkage on joints. As a rule of thumb, a
typical 6" thick slab may shrink 1/8" in every
20". Thus, a 1/8" cut every 20' will eventually open to
1/4". This means the joint has opened 100%. Consider what
this means to a semi-rigid epoxy joint filler that may be able to
accommodate only 5-10% expansion. By bringing your joints closer
together you minimize the degree of filler-to-concrete separation
that will occur.
Now consider random cracking. The larger the slab panel, the
greater the potential for random cracking. It all comes down to a
choice between joints or cracks, and joints are definitely less
expensive than cracks. To cut and properly fill a joint will cost
approximately $2-$2.50/lf, and you have an aesthetically pleasing
floor. And joints are relatively easy to maintain. Random cracks,
on the other hand, are unsightly and will cost $3-$5/lf to cut
out (chase) and fill. And cracks are much more difficult and
expensive to maintain than joints.
Now lets talk about the panel shape. Concrete shrinkage causes an
even stress build-up across the slab. Thus, a 15'x15' panel
shrinks equally across all directions. But if you have a 15'x20'
panel, the stress will be greater across the 20' dimension. It is
quite likely a crack will occur dividing the 20' span into two
10' segments.
The bottom line is this: you have a choice between joints or
cracks. You can reduce the effects of cracking by heavily
reinforcing the slab. But reinforcing does not prevent
cracks...it merely holds them tight at best. And reinforcing
costs money. You need to consider the trade-offs carefully in
your design.
5. The Myths of
Mesh
The first myth about mesh is that it will prevent cracking. It
doesn't. It merely holds the cracks tight, if properly placed.
The second myth is that mesh adds compressive strength to the
slab, if properly placed. It doesn't. The third is that the mesh
can be properly placed, as in the top half of the slab. If you
were to core 100 projects, I guarantee you will find the mesh on
the grade or in the bottom half of the slab about 90% of the
time. In view of this, why specify mesh at all? If you need to
reinforce the slab, consider using reinforcing bars chaired to
the proper height.

Effects of Mesh Near Bottom
One more point should be made about mesh. If it does end up in
the bottom half of the slab, it may actually add to both the
frequency of cracking and the surface width of your cracks. And
you paid extra for this.
6. Dowel the
Construction Joints
The ideal floor is one where all slab panels work together in
unison as traffic passes over the joints. Construction joints
create a total separation between panels, thus creating the
potential for one panel to deflect under load while the adjacent
panel stays up, resulting in joint edge spalling. The use of
smooth dowels at construction joints can assure that both panels
work together under load.
To be effective dowels must be properly spaced and aligned and
greased on one end to allow for joint movement.
7. Construction
Joints Should Be Saw Cut
Construction joints have two major disadvantages.
a. The edges may be inherently weak because
they are finished less densely than the rest of the surface.
b. Unlike a saw cut joint, there is no base to support the
eventual joint filler.
We recommend that all construction joints in traffic paths be saw
cut to a depth of 1'. Saw cutting removes (or at least reveals)
weak edges and creates a base for the filler. Additionally, saw
cut joints will look neater and stand up to traffic longer
without maintenance.
8. Don't
Over-Specify Flatness
Some owners and designers specify higher flatness numbers than
they really need. There are several disadvantages to this
practice:
a. A higher flatness number will result in
higher concrete bids
b. If the flatness number is too high, the concrete contractor
assumes that flatness is the primary criteria for the floor.
Durability must always be the primary criteria of any floor.
Before you specify a flatness number we suggest that an
acceptable existing floor be tested. Many, if not most,
conventional warehouse floors can get by with a F35-40. If no
acceptable floor is available to measure, contact a flatness
consultant such as FACE Consulting (1-800-FNUMBER) for advice and
assistance.
9. Joints at
Doorways Through Walls
Joints where two separate slabs meet at doorways, such as at fire
walls or into separate storage rooms (coolers, etc.), are
frequently found to be suffering severe spalling. Sometimes the
cause is that this was a butted joint and never filled. In some
cases the designer used a premolded filler to isolate the two
slabs. Both approaches are wrong and inappropriate. If hard
wheeled vehicles will pass over this junction, an armored joint
should be provided. The most durable armoring is usually a steel
angle assembly.

10. Properly
Specifying the Floor Joint Filling
Some owners and designers still tend to treat floor joint filling
as an afterthought, something incidental to the actual floor.
This thinking fails to recognize that;
a. Because joints are an interruption in
the surface, joint filling must be considered as a vital link in
the floor surface system.
b. Each joint is a potential impact point for the wheels of
material handling vehicles.
c. Since joints will continue to open for a year or two during
the extended shrinkage period of the floor, joints are in effect
the most vulnerable part of the floor surface.
Our literature contains extensive technical information on floor
joint filling, so I won't duplicate that information here. But
several critical points need to be reinforced;
a. Joint fillers should be specified in
Section 03250, not 07900. This helps make the distinction that
floor joints are to be "filled," not
"sealed."
b. To be effective as an edge protector, the filler must fill the
entire saw-cut, taking advantage of the support offered by the
base of the saw cut. Specify clearly that the filler must be
installed full depth with no compressible backer rod allowed, and
provide proper details in your structural drawings.
c. Do not merely specify "Product X or equal." By doing
so you are tacitly implying that joint filling is not one of your
major concerns. There are more than sixty semi-rigid fillers on
the market, with dramatic variables in their quality and cost. If
you allow an unnamed "equal," you will likely end up
with the cheapest filler, not the best filler for you floor.
d. The filler(s) you specify must match the operational demands
of the floor. Fillers fall into two categories; heavy duty and
moderate duty. If your facility will have heavy loads, hard
(solid) wheels, or frequent traffic, specify a heavy duty filler
by name.
When preparing your bid documents, remember this: the filling of
joints with the most expensive product on the market will cost
you $1.25 to $1.75/lf. The repair of a joint allowed to spall due
to improper filler or filler installation will cost $3-$10/lf.,
not to mention the downtime for repairs.
Joint filling is the last place you want to cut corners.
PROBLEMS IN THE BIDDING PHASE
11. Pre-Qualify
Your Concrete Contractors
With the introduction of equipment such as the Lazer Screed¨*
many new concrete contractors have emerged. But floor
construction remains as much art as science, and there is no
substitute for experience. We recommend that concrete contractors
be pre-qualified. Ask them to identify a few projects that are
4-5 years old, and talk to the owners. Your floor is too valuable
to risk to an inexperienced contractor.
12. Hold a Pre-Bid
Conference
Meet with your short-listed contractors before the bids are
taken. Stress your demands for quality, discuss schedules, job
conditions, availability of good aggregate, specs and drawings,
etc. Listen to recommendations made, and make the contractors
justify their reasons.
PROBLEMS IN THE CONSTRUCTION PHASE
13. Hold a
Pre-Construction Conference
At least one week before the start of work hold a jobsite
conference. Insist on the attendance of the owner, designer,
GC/CM, concrete contractor, ready mix supplier, accessory
suppliers (additives, joint fillers, etc.), the testing lab and
any trades whose work might interfere with or affect the floor
placement. This will be your last opportunity to discuss job
conditions, mix design, schedules, pour sequence, light and
ventilation, temperature, access, curing, etc. Raise all
questions now rather than after the work starts.
14. Inspect the
Finish Grade
The importance of a well compacted, even grade cannot be
overstated. The base must have no hard or soft spots, no high or
low points. Inconsistencies will cause sub-grade drag which will
result in cracking. The best verification of adequate finished
grade is to proof-roll it with a heavy vehicle such as a cement
truck.

15. Start Curing
Procedures Promptly
Once the finishing is complete, the curing process should begin
immediately. Retention of moisture is critical to ensure complete
cement hydration, which yields stronger and more durable
concrete.
Our preference for curing is the use of a moisture retention
sheet for at least seven days. We have seen the best experience
with sheets having one plastic face and the opposite face of
burlap or a synthetic absorptive material. The concrete should be
re-misted whenever the sheet is temporarily removed (for cutting,
etc.) or as dictated by conditions.
16. Cutting of
Contraction (Control) Joints
The most difficult element in cutting is the timing. This is one
prime example of the art/science equation. Cut too early and
joint edges will ravel. Cut too late and the slab may already be
cracking due to tensile stress brought about by shrinkage.
We are advocates of the new breed of early cut saws which are
used within the first few hours after final finishing. There are
three important things to remember in the cutting operation;
a. The timing should be such that the cut
is clean, not disturbing the adjacent aggregate.
b. The blade should be appropriate for the aggregate it must cut
through.
c. The base plate of the saw must be replaced in strict
compliance with the saw manufacturer's instructions. Failure to
comply can result in micro-fracturing of the joint edges.
.......................
........................Micro-Fracturing...............Joint Edge Ravel from Early
Cutting......
Some in the industry prefer to use
the early-cut saws to relieve the slabs surface tension, then
come back later and re-cut the joints with a conventional saw.
This can be a good practice if the slab did not crack beneath the
cut, or if there is evidence of micro-fracturing on the edges.
17. Avoid Premature
Loading on Slabs
Concrete does not usually reach its optimum compressive strength
until 14-28 days. It is always wise to avoid or at least minimize
heavy loads ( rack delivery, etc.) until the slab has reached
adequate strength. If access must be granted, insist that
material handling vehicles have pneumatic tires. All vehicles
crossing the slab should be diapered to prevent oil stains.
In the case of tilt-up construction, the push for access is
intense. If at all possible, keep ready-mix trucks and cranes off
the floors and especially off panel corners. If this is not
possible, try to restrict access lanes to the older pours.

Cracking Caused By
Crane Outrigger
18. Proper
Filling of Floor Joints
Assuming your specs and details have been properly prepared, the
next critical issue in joint filling is the timing. Concrete will
have significant shrinkage for a period of 1-2 years. As
shrinkage occurs, the joints grow wider. Thus, you should delay
your joint filling until the last possible opportunity. In this
manner you will minimize the amount of filler-to-concrete
separation that occurs.
After timing, the most critical element in filling is the depth
of the filler. As cited earlier, a filler is most supportive of
loads when the filler itself is supported by the bottom of a saw
cut.
Our surveys indicate that more than 70% of all projects suffer
cheating in the filler installation. Refer to our article Cheating on Industrial Floor
Joint Filling for a complete
explanation of why cheating occurs and how to prevent and detect
it.
Another important issue is the finished profile of the filler.
Since one goal in filling is to avoid impact points, a filler
should be finished flush with the floor surface. This is best
achieved by over-filling, allowing the filler to cure into a
solid, then shaving the filler off flush with a razor.
19. Provide for
Correction of Filler-to-Concrete Separation
No matter how long you are able to defer your filler
installation, filler-to-concrete separation will still occur.
This is because a filler that is firm enough to support traffic
cannot be flexible enough to accommodate significant joint
opening.
There are two basic means of providing correction of separation;
a. Provide in your specs a call-back
provision, obligating the installer to return to the project six
months after occupancy to refill all voids credit card width or
greater.
Or
b. Have the owner accept responsibility for refilling separation
as part of his maintenance operations. For further discussion of
this subject and the refilling process see our technical sheet T5, Separation,
Causes;Corrections.

Joint Filler
Separation
20. Use
Common Sense in Crack Correction
There are very few slabs placed that do not have cracks.
Hairline, occasional cracks need not necessarily be of concern,
since aggregate interlock will keep the panel structurally
sufficient. If numerous cracks occur, or if cracks are wider than
hairline, an evaluation is called for.
One problem we frequently see is the practice of filling cracks
with a structural epoxy, with the idea of welding the slab back
together. This procedure is often done by pressure injecting
epoxy into drilled port holes. The trouble comes in the fact that
the crack may still be active. If you weld an active crack, you
will likely develop a new crack adjacent to the repaired one. Our
advice is generally not to structurally weld any crack (or joint)
if it can be avoided.
(For more information, see our "Guide to Basic Floor Repairs.")
Summary
Clearly, the twenty recommendations offered in this article won't
prevent all floor problems. But they may help avoid very common
and very preventable problems that occur over and over. We hope
you find this article of value and further hope you will call or
write us if we can help you in any way to achieve higher quality,
more durable industrial floors.
Copyright 2001 Metzger/McGuire
.. ..
|