Home        Products       Services       Locate a Distributor     Repair Products & Info     Custom Colors

 

Section 03252 / Section 03300 / Section 07900 (Cross Reference)

 

SPECIFICATION FOR AMBIENT TEMP SPAL-PRO 2000 INSTALLATION

 

PART 1 - GENERAL

1.01 General Description of Work

Provide all labor, products and equipment required to properly install semi-rigid filler in joints in the interior concrete floor slabs.

1.02. Scope of Work

Fill all contraction (control) and construction (formed) joints in the interior concrete floor slab where the joints will be exposed to material handling vehicle wheels. Refer to drawings for additional joints possibly requiring filler, such as joints under racks,joints at column diamonds and pads, etc.

1.03. Work Excluded

This section specifically excludes all caulking and sealant work specified in Section 7900. Refer to 7900 to determine responsibility for filling/sealing isolation joints where slab joins walls or column pads, expansion joints, etc.

1.04. Applicable Standards

Products and installation shall be in compliance or exceed the joint filling criteria established in the latest ACI 302 and ACI 360 Committee published documents and all manufacturers instructions and technical literature.

1.05 Contractor Qualifications

Installer shall have a minimum of three (3) years experience in the installation of semi-rigid fillers on industrial floors.

 

2. PRODUCTS

2.01 Product(s)

Joint filler shall be Spal-Pro 2000, a heavy duty, semi-rigid polyurea manufactured by Metzger/McGuire, Concord, NH (800-223-6680). No substitutes will be allowed. Material shall be brought to site in original, unopened containers. Product will be stored in temperatures between 50-80 degrees F.

2.02 Accessories

Silica sand may be used at contractor’s option to choke-off shrinkage cracks beneath filler. Silica must dry, bagged of 20 to 40 grit. Compressible backer use is prohibited other than for non-saw cut construction joints. Refer to installation section for additional information.

3. EXECUTION

3.01 Project Conditions

Work area should be free of obstructions and other trades. Slab should be visibly dry and not be scrubbed for at least 24 hours prior to filler installation. Air temperature should be greater than 40 degrees F for 24 hours prior to filling.

3.02 Timing of Installation

ACI recommends that filling be deferred as long as possible to allow for maximum slab shrinkage and joint widening. 90-120 day slab cure is advisable. Deferring filling until after facility is under permanent temperature control is best.

3.03 Examination of Conditions

It is the responsibility of the installer to inspect the project and joint conditions and notify on-site management in writing of any deficiencies that might adversely affect the quality or durability of the work performed or his contract price. Start of work by the installer implies acceptance of conditions.

3.04 Pre-Installation Sample

Before start of actual work contractor shall install samples to demonstrate his intended procedures and finished product. Sample shall include at least 25’ each of both contraction and construction joints in the presence of on-site management. If procedures and finished product are approved they will be considered a standard for the entire project.

3.05 Joint Preparation

All saw-cut joints shall be thoroughly cleaned to their full depth or 2” minimum, whichever is lesser. Construction (formed) joints that are not sawn shall be cleaned to a minimum depth of 2”. Preparation shall be performed using a vacuum-equipped saw that will reach the 2” minimum depth, and shall be used in a manner that takes both joint walls back to bare concrete, removing all saw laitance, curing compounds, sealers, debris, etc. Where joints have minor edge chips, said chips will be “squared off” and filled along with the joint itself.

3.06 Choking-Off Joint Bottom

The installer may, at his option, use a maximum of 1/4” of silica sand placed at the bottom of the saw-cut joints to prevent filler run-thru into the shrinkage crack. Compressible backer rod is prohibited in saw-cut joints unless they exceed 2” deep. Compressible backer rod may be used in through-slab(non-sawn) construction joints but must be recessed at least 2” below the slab surface.

Caution: The use of backer rod in any saw-cut joints less than 2” deep will result in the rejection of all saw-cut joints work.

3.07 Filler Installation

  a. Properly clean joints as described in section 3.05

  b. Install silica sand (contractors option) at base of

     joint, or backer rod as allowed and limited in 3.06.

  c. Pre-mix the “A” component to re-disburse any

     settlement that occurred in shipping or storage.

  d. Due to it’s rapid gel time Spal-Pro 2000 must be        

     dispensed via power pump (dual-feed line system) or        

     from dual-cartridge units pre-packaged by

     Metzger/McGuire.

  e. Dispense Spal-Pro 2000 in one continual bead, filling

     from bottom to top until joint is overfilled (crowned).

     Allow to cure into a solid.

  f. After Spal-Pro 2000 cures into a solid, razor-off

     overfill to leave a flush filler profile.


3.08 Finished Profile

A flush filler profile is vital for maximum joint protection. If profile is concave (below floor surface), abrade Spal-Pro 2000 surface and apply a cap bead (crowned), allow to cure, then razor flush.